109
13.9 Complete the electrical floor plan for the wiring of convenience outlets in a
room as shown in the floor plan that follows. Section 13.8.1 provides the
suggested loads for general purpose outlets, which is 1.5A per outlet, or 3A
per duplex outlet. If an outlet is identified to serve a specific equipment, then
the load for that outlet shall be based on the nameplate rating of the
equipment, for example, a TV, a computer, etc. For purpose of this problem,
the load at each receptacle is identified as follows:
C – general purpose receptacle 3A
D – special equipment 5A
E – special equipment 10A
Step 2
Prepare the conduit plan indicating the
conduit connections between electrical
devices (fixtures and switches) to be
wired.