Chap. 10 Spread Footings-Structural Design
10.12 A 12–in wide concrete block wall carries an unfactored vertical design load of 25.1 k/ft. The
sustained vertical load for serviceability analysis is 18.4 k/ft. It is to be supported on a
continuous footing made of 2500 lb/in2 concrete and 40 k/in2 steel. The soil has an allowable
bearing pressure for bearing capacity of 6700 lb/ft2 (using ASD methods) and an allowable
bearing pressure for settlement of 4000 lb/ft2. The groundwater table is at a great depth. The
local building code requires that the bottom of this footing be at least 24 inches below the ground
surface. Determine the required footing width, thickness, and design the lateral and longitudinal
steel. Show your design in a sketch.
Solution
Per problem statement use D = 24 in. = 2 ft.
Compute required thickness
( )( )
( )( )( ) ( )( )
‘
2
()
From Eq. 10.27
48 2
25,100 lb/ft. 60 in. 12 in.
48 0.75 12 in. 2500 lb/in 2 25,100 lb/ft
17 in.
u
wc u
PB c
d
bf P
φ
–
=+
–
=+
=
Design lateral steel